ANALISIS PENGARUH HARMONISA PADA TRANSFORMATOR BHT01 DAN BHT02 RSG GA. SIWABESSY

Koes Indrakoesoema, KI and Andriyanto, Yayan (2016) ANALISIS PENGARUH HARMONISA PADA TRANSFORMATOR BHT01 DAN BHT02 RSG GA. SIWABESSY. Prosiding Seminar Nasional Teknologi dan Aplikasi Reaktor Nuklir. ISSN 976-602-6423-00-9

[thumbnail of 7_Koes Indra.pdf]
Preview
Text
7_Koes Indra.pdf

Download (733kB) | Preview

Abstract

ANALISIS PENGARUH HARMONISA PADA TRANSFORMATOR BHT01 DAN BHT02 RSG GA SIWABESSY. Tingkat harmonisa yang tinggi sangat berpengaruh pada transformator, dan kinerja transformator daya ditentukan melalui parameter rugi-rugi daya. Penurunan kinerja transformator dipengaruhi oleh munculnya harmonisa yang akan berpengaruh pada losses dan penurunan kapasitas kerja transformator (derating). Beban-beban yang dicatu melalui transformator BHT01 dan BHT02 kebanyakan adalah motor-motor induksi sehinga keberadaan beban non linier pada sistem tenaga listrik akan menimbulkan efek harmonisa. Pada penelitian ini dilakukan pengukuran harmonisa tegangan dan harmonisa arus serta komponen-komponen harmonisanya menggunakan Power Quality Analyzer Hioki 3169-20 dengan beban penuh pada jalur BHA dan BHB (transformator BHT01 dan BHT02). Metode analisa yang dipergunakan adalah metoda komparasi antara hasil pengukuran dengan standar IEEE 519-1992, sebagai evaluasi terhadap kualitas daya listrik pada transformator BHT01 dan BHT02 dan dihitung kenaikan rugi-rugi trafo akibat beban yang mengandung harmonik. Hasil pengukuran menunjukkan bahwa Total Harmonic Distortion tegangan (%THDv) terendah pada BHT01 adalah 1,07% pada fasa S dan tertinggi adalah 1,90% pada fasa R, sedangkan %THDv pada BHT02 terendah adalah 1,05% pada fasa T dan tertinggi adalah 2,08% pada fasa R. Nilai-nilai di atas masih dibawah standar IEEE 519-1992 (5%). Total Harmonic Distortion arus (%THDi) pada BHT01 adalah terendah 1,21% pada fasa S dan tertinggi 8,22% pada fasa R, sedangkan %THDi pada BHT02, terendah 1,33% pada fasa S dan tertinggi 10,29% pada fasa S. Sehingga untuk BHT01 pada fasa R dan BHT02 pada fasa S melebihi standar IEEE 519-1992 (8%). Kenaikan rugi-rugi transformator akibat harmonisa pada BHT01 adalah rugi tembaga 0,093% dan rugi arus Eddy 0,23% sedangkan pada BHT02, kenaikan rugi tembaga adalah 0,047% dan rugi arus Eddy 0,11%.
Kata kunci : Transformator, THD (Total Harmonic Distortion), Derating
ABSTRACT
ANALYSIS OF HARMONICS AFFECT ON TRANSFORMER BHT01 AND BHT02 RSG GA SIWABESSY. High level of harmonics can affect the transformer, and the performance of power transformer can be determined through power loss parameter. Degradation of Transformer which influenced of harmonics will affect the losses and reduction of capacity transformer (derating). Loads are supplied from a transformer BHT01 and BHT02 mostly induction motors so that the existence of non-linear loads on the power system will generate harmonics effects. The research was done by measurement the voltage harmonics (% THDv) and current harmonics (% THDi) as well as the harmonics content by the Power Quality Analyzer using Hioki 3169-20 under load conditions on the line BHA and BHB (transformer BHT01 and BHT02). The comparison method between the result of measurements with the IEEE 519-1992 standard is used to analyze, as an evaluation the quality of electric power of transformers BHT01 and BHT02 and calculated the increase of losses transformer due to the load containing harmonics. The result of measurement was indicated that the lowest Total Harmonic Distortion of voltage (THDv) BHT01 is 1.07% in phase S and the highest is 1.90% in phase R. For BHT02, the lowest is 1.05% in phase T and the highest is 2.08% in phase R. The harmonic content of the transformer for THDv was below the standard (< 5%). Total Harmonic Distortion of current (%THDi) of BHT01, the lowest is 1.21% in phase S and the highest is 8.22% in phase R while in BHT02, the lowest is 1.33% and the highest is 10.29%, both is phase S. One phase of %THDi in BHT01 and BHT02 more than standard (8%), so the increase of Cu losses is 0.093% and Eddy current losses is 0.23% for BHT01 and for BHT02, Cu losses is 0.047% and Eddy current losses is 0.11%.
Keywords: Transformer, Total Harmonic Distortion (THD), Derating

Item Type: Article
Subjects: Taksonomi BATAN > Reaktor Nuklir > Teknologi Reaktor > Sistem Reaktor
Taksonomi BATAN > Reaktor Nuklir > Teknologi Reaktor > Sistem Reaktor
Divisions: BATAN > Pusat Reaktor Serba Guna
IPTEK > BATAN > Pusat Reaktor Serba Guna
Depositing User: Administrator Repository
Date Deposited: 30 Oct 2018 02:28
Last Modified: 31 May 2022 04:44
URI: https://karya.brin.go.id/id/eprint/4173

Actions (login required)

View Item
View Item