EVALUASI PENGELOLAAN KIMIA AIR PENDINGIN PRIMER REAKTOR KARTINI, REAKTOR TRIGA 2000 DAN REAKTOR G.A. SIWABESSY Sumijanto

Sumijanto, ST (2003) EVALUASI PENGELOLAAN KIMIA AIR PENDINGIN PRIMER REAKTOR KARTINI, REAKTOR TRIGA 2000 DAN REAKTOR G.A. SIWABESSY Sumijanto. In: Prosiding Presentasi Ilmiah Teknologi Keselamatan Nuklir VIII ISSN No. 1410-0533, 26 dan 27 Pebruari 2003, Pusat Teknologi dan Keselamatan Reaktor Nuklir.

Full text not available from this repository.

Abstract

ABSTRAK
EVALUASI PENGELOLAAN KIMIA AIR PENDINGIN PRIMER REAKTOR KARTINI, REAKTOR TRIGA 2000 DAN REAKTOR G.A. SIWABESSY. Telah dilakukan evaluasi terhadap pengelolaan kimia air pendingin primer reaktor riset BATAN. Evaluasi didasarkan atas data pengelolaan kimia air pendingin primer yang diperoleh melalui survei pada masing masing reaktor. Tujuan dari evaluasi ini adalah untuk penilaian apakah penanganan kimia air pendingin primer telah memadai sehingga dapat menghasilkan mutu air pendingin primer yang memenuhi persyaratan keselamatan operasi yang diharapkan. Dari hasil survei yang dilakukan ditemukan adanya beberapa kekurangan dalam pengelolaan kimia air pendingin primer yang diantaranya adalah : a).Sistem purifikasi air pendingin primer dioperasikan saat reaktor operasi sedangkan saat reaktor tidak operasi sering tidak dioperasikan, b).Dalam air pendingin primer reaktor Triga 2000 kandungan Si melampaui batas yang diijinkan, c).Beberapa parameter kimia air belum digunakan sebagai indikator mutu air pendingin primer seperti Cl- , Si , oksigen dan logam berat seperti Cu, Cd dll , d).Analisis unsur kelumit dalam air pendingin primer reaktor G.A. Siwabessy tidak dilakukan karena kemampuan alat hanya sampai tingkat ppm saja sedangkan persyaratan dalam LAK mencapai tingkat ppb. Dari evaluasi data tersebut dan dengan mengacu parameter operasi kimia air pendingin primer reaktor riset EWA 10 MW disimpulkan bahwa untuk dapat memperoleh mutu air pendingin primer yang lebih baik dari kondisi sekarang maka pengelolaan kimia air pendingin primer reaktor riset BATAN perlu ditingkatkan.
ABSTRACT
EVALUATION OF PRIMARY COOLANT WATER CHEMISTRY MANAGEMENT ON KARTINI, TRIGA 2000 AND GA SIWABESSY REACTOR.The evaluation primary coolant water chemistry management on BATAN research reactor has been done. The evaluation based on primary coolant water chemistry management data, through survey on each reactor. The aimof this evaluation is to evaluate what ever primary coolant water chemistry management was reach the good condition that could product quality of primary water coolant which meet safety operation requirement. From survey result was done at found any missing on primary coolant water chemistry management such as a). Purification system in conditions un operation during reactor shutdown. b). Si content in primary coolant of Triga 2000 reactor greater than specification limit. c). Several water chemistry parameter not yet as indication of primary coolant water chemistry such as Cl-, Si, Oxygen and heavy metal such as Cu, Cd etc. The trace analysis in primary water coolant of GA Siwabessy reactor not yet implemented because limited apparatus capacity with the unity in ppm but by safety analysis report should be reads unity in ppb. From by data evaluation and to revere to primary coolant water chemistry operation parameter of 10 MW EWA reactor could summarized that to reach the better primary coolant water qualityfrom recent condition so the management of primary coolant water chemistry of BATAN research reactor must be improved.

Item Type: Conference or Workshop Item (Paper)
Subjects: Taksonomi BATAN > Keselamatan dan Keamanan Nuklir
Taksonomi BATAN > Keselamatan dan Keamanan Nuklir
Divisions: BATAN > Pusat Teknologi dan Keselamatan Reaktor Nuklir
IPTEK > BATAN > Pusat Teknologi dan Keselamatan Reaktor Nuklir
Depositing User: Administrator Repository
Date Deposited: 21 Apr 2020 07:04
Last Modified: 31 May 2022 03:51
URI: https://karya.brin.go.id/id/eprint/9774

Actions (login required)

View Item
View Item