Suroso, S (2002) EVALUASI UNJUK KERJA MENARA PENDINGIN RSG GAS. In: PROSIDING SEMINAR HASIL PENELITIAN P2TRR, PRSG - BATAN.
suroso.pdf
Download (474kB) | Preview
Abstract
EVALUASI UNJUK KERJA MENARA PENDINGIN RSG GAS. Pemanfaatan operasi reaktor harus dilakukan seoptimal mungkin, sehingga perencanaan pengoperasian reaktor yang akan menggunakan hanya dengan sistem pendingin satu jalur harus diantisipasi. Untuk menganalisis unjuk kerja menara pendingin pada kondisi operasi satu jalur dilakukan dengan menggunakan data operasi reaktor daya 10 MW, yang dibandingkan dengan kondisi desain dan hasil peritungan dengan program CATHENA. Hasil perhitungan untuk kondisi desain diperoleh harga perbandingan laju alir air dengan udara sebesar (L/G) =1,52 dan harga number transfer unit (NTU) sebesar 0,348 sedangkan untuk kondisi operasional diperoleh L/G rata-rata sebesar 1,37 dan harga NTU rata-rata sebesar 0,342, sedangkan hasil yang diperoleh dari perhitungan menggunakan program CATHENA harga L/G 1,39 dan NTU sebesar 0,302. Harga unjuk kerja menara pendingin kondisi operasi 91 % dan perhitungan 73 %, hasil unjuk kerja tersebut menunjukkan hasil perhingan lebih rendah dari pada perhitungan.
Kata kunci : evaluasi, menara pendingin, unjuk kerja.
Abstact
EVALUATION OF COOLING TOWER PERFORMANCE RSG-GAS. Utilization of RSG-GAS reactor should be operated as effeiciently as possible, so that reactor operation planning using one line primary coolant can be anticipated. To analyze the performance of the RSG-GAS cooling tower with one line primary coolant doing by using same data from 10 MW thermal reactor operation. The result were then compare to those achieved using CATHENA code. The results indicated that, for design condition the ratio of water flowrate to air is (L/G) 1.52 and number transfer unit (NTU) is 0.348. For operation condition, the average of L/G and NTU are respectively 1.37 and 0,348. Moreover the results achieved by the code showed that L/G and NTU are respectively 1.35 and 0,302. The performance of cooling tower achieved operation condition and the code results are respectively 91 % and 72 %. This means that the calculated results are lower than measurement reasults.
Key word: evaluation, cooling tower, performance
Item Type: | Conference or Workshop Item (Paper) |
---|---|
Subjects: | Taksonomi BATAN > Reaktor Nuklir > Teknologi Reaktor > Fisika Reaktor Taksonomi BATAN > Reaktor Nuklir > Teknologi Reaktor > Fisika Reaktor |
Divisions: | BATAN > Pusat Reaktor Serba Guna IPTEK > BATAN > Pusat Reaktor Serba Guna |
Depositing User: | Administrator Repository |
Date Deposited: | 11 Feb 2019 03:11 |
Last Modified: | 31 May 2022 03:55 |
URI: | https://karya.brin.go.id/id/eprint/8598 |