APLIKASI SCADA DENGAN MEDIA KOMUNIKASI NIRKABEL 2.4 GHz UNTUK PENGENDALI OPERASI FASILITAS KANAL HUBUNG PENYIMPANAN SEMENTARA BAHAN BAKAR NUKLIR BEKAS (KHIPSB3)

Parjono, parjono and Budiyono, Budiyono (2016) APLIKASI SCADA DENGAN MEDIA KOMUNIKASI NIRKABEL 2.4 GHz UNTUK PENGENDALI OPERASI FASILITAS KANAL HUBUNG PENYIMPANAN SEMENTARA BAHAN BAKAR NUKLIR BEKAS (KHIPSB3). PROSIDING SEMINAR NASIONAL TEKNOLOGI PENGELOLAAN LIMBAH XIV. pp. 8-16. ISSN ISSN 1410-6086

[thumbnail of 2016_Parjono_PN.pdf]
Preview
Text
2016_Parjono_PN.pdf

Download (2MB) | Preview

Abstract

ABSTRACT

APLICATION OF SCADA USING WIRELESS COMMUNICATION MEDIA 2.4 GHz FOR CONTROLLING THE
OPERATION OF TRANSFER CHANNEL INTERIM STORAGE FOR SPENT FUEL FACILITY. Interim storage
facility equipment installation Used Nuclear Fuel operated to ensure the safety of humans and the environment.
operating equipment to meet safe limits Operating Conditions should be controlled and monitored. Equipment is
controlled and monitored from a separate location within 500 meters. Both locations have not been there Twice Pair
Unshielded cable networks and fiber optic. Therefore, control and monitoring equipment to implement technology
Programmable Logic Controller integrated with SCADA systems. Apply system 2.4 Ghz wireless network as
communication media SCADA system. Selection of a 2.4 Ghz wireless network or Wifi-G 802.11g wireless standard,
because the media can send and receive data at up to 54 Mbps and has a user tolerance and lower interference than the
5.8 GHz frequency. The system was applied in the context of efficiency, facilitate supervision and control, and data
acquisition .. The method is done by mounting Accest point and Client Bridge, testing the quality of network services or
Quality of service and function testing of applications using MTU- SCADA Simatic Wincc Flexible software. Results of
testing the quality of wireless network services obtained value of 4.35 millisecond delay and packet loss 0%. This value
is included in the category and the degradation is very good by the standards TIPHON. Testing of the SCADA system
with 2.4 GHz wireless communication media have been installed to work properly and optimally.

Keywords: spent fuel, programmable logic control, SCADA, Wirelless,QoS

Item Type: Article
Subjects: Taksonomi BATAN > Daur Bahan Bakar Nuklir dan Bahan Maju > Limbah Radioaktif > Teknik Pengolahan Limbah Radioaktif
Taksonomi BATAN > Daur Bahan Bakar Nuklir dan Bahan Maju > Limbah Radioaktif > Teknik Pengolahan Limbah Radioaktif
Divisions: BATAN > Pusat Teknologi Limbah Radioaktif
IPTEK > BATAN > Pusat Teknologi Limbah Radioaktif
Depositing User: Administrator Repository
Date Deposited: 09 May 2018 06:19
Last Modified: 31 May 2022 04:45
URI: https://karya.brin.go.id/id/eprint/495

Actions (login required)

View Item
View Item